Date Text
2023-04-25 15:56:38.00000SHEET E-01: #10 AWG CONDUCTORS BETWEEN MAIN SERVICE
 PANEL AND TESLA SWITCH ARE UNDERSIZED FOR INDICATED
 OVERCURRENT PROTECTION AND DO NOT INCLUDE AN EQUIPMENT
 GROUNDING CONDUCTOR.
 PLEASE REVIEW ONE-LINE DIAGRAM CAREFULLY PRIOR TO
 SUBMITTING NEXT REVISION.
2023-04-24 09:14:44.00000RESPONSE TO REVISION REQUEST PERMITS@SUNVENA.COM