Plan Review Notes For Permit 22100019
Permit Number 22100019
Review Stop BUILDING
Sequence Number 5
Notes
Date Text
2023-04-18 15:47:29.00000SHEET E-01:
 1] ADD A #6 CU EQUIPMENT GROUNDING CONDUCTOR WITH THE
 FEEDER CONDUCTOR SET BETWEEN THE MAIN SERVICE PANEL AND
 THE TESLA GATEWAY.
 2] THE #2 CU CONDUCTOR BETWEEN THE TESLA GATEWAY AND
 THE INTERIOR SUB PANEL IS UNDERSIZED FOR THE 150A
 OVERCURRENT PROTECTION. CHANGE CONDUCTOR SIZE OR SHOW
 APPROPRIATE OVERCURRENT PROTECTION.
2023-04-18 14:24:24.00000REVISED PLANS PERMITS@SUNVENA.COM