Plan Review Notes For Permit 22081500
Permit Number 22081500
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2023-01-09 14:46:14.00000RECEIVED REVISED ONE-LINE DIAGRAM PROPOSING CHANGING
 SERVICE DISCONNECT (MAIN) BREAKER FROM 150A TO 125A.
 PROPOSED CHANGE IS IN RESPONSE TO A DISAPPROVED
 INSPECTION ON 1/5/23 WITH NOTES AS FOLLOWS:
  
 125% OF INVERTER OUTPUT PLUS MAIN BREAKER RATING (150A)
 EXCEEDS 120% OF BUS RATING.
 THIS IS A 150A RATED BUS (SQ D #QO30MW150)
 7.7 KW STRING INVERTER
  
 THIS ALTERATION IS NOT APPROVED BECAUSE THE 125A
 SERVICE DISCONNECT IS UNDERSIZED FOR THE CALCULATED
 LOAD. THE INCLUDED LOAD CALCULATION SHOWS A TOTAL
 DEMAND OF 32489 VA. 32489/240 = 135 AMPS.
 THERE IS AN ERROR IN THE FINAL LINE OF THE INCLUDED
 LOAD CALCULATION: THE FULL AMOUNT (NOT 50%) OF THE
 DEMAND VA SHOULD BE DIVIDED BY THE SERVICE VOLTAGE IN
 ORDER TO DETERMINE MINIMUM SERVICE AMPACITY.