-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 22080604
Permit Number 22080604
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-08-11 13:45:24.00000SHEET PV-05: CONDUCTORS BETWEEN NEW COMBINER PANEL AND
 NEW PV DISCONNECT ARE NOT IDENTIFIED; CONDUCTOR ID #5
 IS UNDERSIZED FOR 80A OCPD.
 SHEET PV-07: AC LABEL MUST SHOW COMBINED MAXIMUM
 INVERTER OUTPUT (BOTH EXISTING AND PROPOSED SYSTEM AS A
 TOTAL)
2022-08-10 16:08:06.00000PERMITTING@MERAKISOLTUIONS.COM