Plan Review Notes For Permit 22080260
Permit Number 22080260
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2023-05-11 15:14:58.00000MAIN DISTRIBUTION PANEL (AT EXTERIOR SERVICE) REQUIRES
 A MAIN BREAKER NOT EXCEEDING 400 AMPS. THE SUBMITTED
 SCHEDULE SHOWS THIS AS A "MAIN LUG ONLY" PANEL.
2023-05-11 15:13:36.00000ELECTRICAL ONE-LINE DIAGRAM & PANEL SCHEDULES ONLY