2022-11-21 13:40:18.00000PLANS ARE COMPLETE, BUT A CLARIFICATION/REVISION IS
 REQUIRED ON THE ONE-LINE ELECTRICAL DIAGRAM:
 SHOW OVERCURRENT PROTECTION USED FOR #6 CONDUCTORS
 BETWEEN GENERATOR AND MDP. THE 100A BACKFED BREAKER
 PROPOSED FOR THE MDP IS OVERSIZED FOR #6. CHANGE
 CONDUCTOR TO MIN #3 CU OR CHANGE BACKFED BREAKER TO 60
 AMP.
 NOTE THAT THE SPECIFICATIONS FOR THE GENERATOR INDICATE
 20KW. AFTER A REVIEW OF THE MANUFACTURER'S WEBSITE, IT
 IS UNCLEAR IF THIS IS MAXIMUM DC INPUT OR MAXIMUM AC
 OUTPUT. IT IS ALSO UNCLEAR IF THERE IS ANY BUILT-IN AC
 OUTPUT OVERCURRENT PROTECTION ON THE GENERATOR; IF SO,
 THIS WILL DETERMINE THE OUTPUT CONDUCTOR SIZE AND THE
 BACKFED BREAKER SIZE.
  