Date Text
2022-09-23 13:38:11.000001] 20 KW INVERTER OUTPUT REQUIRES MIN 110A OVERCURRENT
 DEVICE SUPPLIED BY MINIMUM #2 COPPER. PV CIRCUITS ARE
 CONSIDERED CONTINUOUS PER 690.8 (B). (20000/240) X 1.25
 = 104 AMPS. REQUIREMENT CAN BE WAIVED IF MANUFACTURER
 DOCUMENTATION SHOWS THE SYSTEM TESTED AND LISTED TO BE
 USED IN CONJUNCTION WITH 100 AMP OVERCURRENT
 PROTECTION.
 2] STILL NEED SPECIFICATION SHEET FOR INTERLOCK KIT.