Plan Review Notes For Permit 22071374
Permit Number 22071374
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-07-26 14:19:12.000001] PROVIDE ROOF PLAN VIEW SHOWING PLACEMENT OF MODULES
 IN RELATION TO EACH EAVE, RIDGE, HIP, OR VALLEY.
 INDICATE THESE DIMENSIONS ON PLAN; MAINTAIN COMPLIANCE
 WITH FLORIDA FIRE PREVENTION CODE 11.12.2.2.2 PROVIDING
 FOR FIRE ACCESS PATHS.
 2] PROVIDE ADDITIONAL SPECIFICATION SHEET(S) FOR POWERX
 GENERATOR, INCLUDING MANUFACTURER GUIDELINES FOR
 INSTALLATION. SPECIFICATION SHEETS SHOULD INCLUDE
 ENOUGH DETAIL TO DETERMINE ONBOARD OVERCURRENT
 PROTECTION AND DISCONNECTING MEANS, AND SHOULD SHOW
 TYPICAL CONNECTION DIAGRAMS FOR FIELD-INSTALLED WIRING.
 3] PROVIDE ONE-LINE ELECTRICAL DIAGRAM SHOWING ALL
 FIELD-INSTALLED WIRING. DIAGRAM MUST INDICATE CONDUCTOR
 AND RACEWAY TYPES AND SIZES, ALONG WITH TERMINATIONS TO
 ALL MAJOR COMPONENTS.
2022-07-26 08:36:47.00000EMAILED IN FORM OWNER, R.PETROVICH@ICLOUD.COM
 NEEDS VALUATION OF JOB