Date Text
2022-06-13 13:12:08.000001] SHEET PV05: CONDUCTORS #4 AND #5 INCORRECT. MINIMUM
 AMPACITY = 83.3. USE #4 CU WITH 90A FUSES OR #3 CU WITH
 100A FUSES.
 2] SHEET PV07: SHOW ADDITIONAL AC CURRENT LABEL
 INDICATING TOTAL SYSTEM OUTPUT (COMBINED EXISTING PLUS
 PROPOSED SYSTEM OUTPUT).