Date Text
2022-08-09 17:05:34.00000SHEET E-4: AC CURRENT LABEL SHOULD SHOW ACTUAL INVERTER
 OUTPUT OF 47.5 AMPS PER 690.54. DO NOT ADD A 25%
 CONTINUOUS LOAD FACTOR TO THIS LABEL; CONTINUOUS LOAD
 FACTOR APPLIES TO CIRCUIT COMPONENTS ONLY PER 690.8
 (B). THIS NOTE HAS BEEN REPEATEDLY INSERTED ON THIS
 CONTRACTOR'S PREVIOUS PLAN REVIEWS.
2022-08-07 10:58:09.00000REVISED PLAND FLPERMITS@VISIONSOLAR.COM