-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 22051302
Permit Number 22051302
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2022-08-09 16:55:39.00000SHEET E-4: AC CURRENT LABEL SHOULD SHOW ACTUAL INVERTER
 OUTPUT OF 25 AMPS PER 690.54. DO NOT ADD A 25%
 CONTINUOUS LOAD FACTOR TO THIS LABEL; CONTINUOUS LOAD
 FACTOR APPLIES TO CIRCUIT COMPONENTS ONLY PER 690.8
 (B). THIS NOTE HAS BEEN REPEATEDLY INSERTED ON THIS
 CONTRACTOR'S PREVIOUS PLAN REVIEWS.
2022-08-07 10:57:16.00000REVISED PLANS EMAILED IN FLPERMITS@VISIONSOLAR.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved