Plan Review Notes For Permit 22040228
Permit Number 22040228
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-04-11 16:30:01.000001] CONDUCTOR SET #1 MUST INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR BASED ON T250.122
 2] IDENTIFY CONDUCTOR SET #4 INCLUDING EQUIPMENT
 GROUNDING CONDUCTOR
 3] INCLUDE NOTE STATING THAT GROUNDS/NEUTRALS WILL BE
 ELECTRICALLY SEPARATED IN ATS
 4] SHOW SERVICE GROUNDING ELECTRODE CONDUCTOR
 TERMINATED IN MDP, NOT IN CT METER SOCKET; SHOW SIZE OF
 THIS CONDUCTOR
 5] SHOW BOTH TRANSFORMER GROUNDING ELECTRODE CONDUCTOR
 SIZES. THESE CONDUCTORS MUST BE BASED ON THE DERIVED
 (SECONDARY) CONDUCTORS, AND SIZED PER TABLE 250.102
 (C)(1).