2022-04-07 15:57:54.000001] CLARIFICATION REQUIRED ON SHEET E1. CONDUIT #3 FROM
 MAIN HOUSE ARRAY TO COMBINER CONTAINS TWO #10
 CURRENT-CARRYING CONDUCTORS TERMINATING INTO A 2-POLE
 20A BREAKER. ARE ALL 16 MICROINVERTERS INTENDED TO
 SUPPLY A SINGLE STRING? IF SO, 125% OF THE COMBINED
 INVERTER OUTPUT EXCEEDS THE RATING OF THE 20A BREAKER.
 NOTES INSIDE THE COMBINER INDICATE "TWO" 20A BREAKERS
 FOR THIS APPLICATION. PLEASE CLEARLY INDICATE THE
 INTENDED STRING CIRCUITRY AND OVERCURRENT PROTECTION.
  
 2] SHOW A GROUNDING ELECTRODE SYSTEM COMPLYING WITH
 PART III OF ARTICLE 250 AT THE SHED PV DISCONNECT.
 STRUCTURES SUPPORTING A PV ARRAY MUST HAVE A GROUNDING
 ELECTRODE SYSTEM; SEE 690.47.