Date Text
2022-03-25 15:58:45.00000SHEET W001: SHOW SIZE OF BACKFED CIRCUIT BREAKER USED
 FOR PV INTERCONNECTION
 SHEET L001: REMOVE TWO AC CURRENT/VOLTAGE LABELS
 SHOWING INCORRECT CURRENT. MAXIMUM OUTPUT OF THE
 PROPOSED SYSTEM IS 22 AMPS (ROUNDED).
 SHEET L001: INCLUDE RAPID SHUTDOWN GRAPHIC LABEL PER
 NEC FIGURE 690.56 (C)(1)(A).
 REPLACE ONLY THE TWO AFFECTED SHEETS, NOT THE ENTIRE
 SET OF PLANS.