Plan Review Notes For Permit 22020811
Permit Number 22020811
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-03-09 15:22:26.00000SHEET E-01: CONDUCTORS BETWEEN COMBINER PANEL AND
 SUPPLY-SIDE TAP (VIA PV DISCONNECT) MUST HAVE AN
 MINIMUM AMPACITY OF 98 AMPS BASED ON 75 DEGREE C
 TERMINAL RATINGS. CHANGE THIS CONDUCTOR TO MINIMUM #3
 CU.