Plan Review Notes For Permit 22020699
Permit Number 22020699
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2022-04-19 16:35:07.00000SHEET E2: CONDUCTORS BETWEEN COMBINER PANEL AND MAIN
 SERVICE PANEL (ID #5 & 6) MUST HAVE A MINIMUM AMPACITY
 OF 36.3 AT 75 DEGREES C. CHANGE TO MINIMUM #8 CU. SEE
 TABLE 310.15 (B)(16).