Plan Review Notes
Plan Review Notes For Permit 22020035
Permit Number 22020035
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2022-10-27 15:40:57.00000REFER TO SHEET E-1 FOR THE FOLLOWING COMMENTS:
 1] SHOW TRANSFORMER GROUNDING ELECTRODE CONNECTION TO
 EXISTING (OR REPLACED) BUILDING SERVICE GROUNDING
 ELECTRODE. SHOW GROUNDING ELECTRODE CONDUCTOR SIZE
 BETWEEN TRANSFORMER AND BUILDING ELECTRODE. 250.30
 (A)(4), TABLE 250.66.
 2] TRANSFORMER SECONDARY PROTECTION MUST NOT EXCEED
 250% OF RATED SECONDARY OUTPUT. FOR THIS PURPOSE, THE
 SECONDARY IS IDENTIFIED AS CONNECTING TO THE UTILITY
 WITH 240 VOLTS 3-PHASE. TABLE 450.3 (B).
 3] SHOW PERMANENT LABEL ON TRANSFORMER INDICATING THE
 LOCATION OF THE PRIMARY DISCONNECTING MEANS, OR INSTALL
 UNFUSED PRIMARY DISCONNECT WITHIN SIGHT OF TRANSFORMER.
 FOR THIS PURPOSE, THE PRIMARY IS IDENTIFIED AS
 CONNECTING TO THE INVERTER. 450.14.
 4] IT IS RECOGNIZED FROM PREVIOUS INSPECTIONS THAT
 CONDUCTOR ID #6 IN THE TRENCH DOES NOT INCLUDE AN
 EQUIPMENT GROUNDING CONDUCTOR AS SHOWN ON THE PLANS.
 THIS SET OF CONDUCTORS CONSISTS OF ONLY FOUR INSULATED
 WIRES; AS SUCH, IT IS NOT POSSIBLE TO
 PROVIDE BOTH A NEUTRAL AND AN EQUIPMENT GROUND BETWEEN
 THE INVERTER AND THE TRANSFORMER. AN EQUIPMENT GROUND
 IS MANDATORY; VERIFY MANUFACTURER REQUIREMENT FOR
 INVERTER OPERATION WITHOUT A NEUTRAL CONDUCTOR.