2022-02-14 11:18:09.00000FDC SHALL BE MOVED TO A FREE-STANDING LOCATION AWAY
 FROM THE COLLAPSE ZONE. A SIGN SHALL BE IN THE AREA, TO
 IDENTIFY THE FDC. EVALUATION OF THE PIV AND HYDRANTS
 SHALL BE PERFORMED AND A REPORT SHALL BE SUBMITTED TO
 THE FIRE MARSHAL'S OFFICE.