Plan Review Notes
Plan Review Notes For Permit 21100276
Permit Number 21100276
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2021-10-18 14:14:15.00000ITEM #1 ON PREVIOUS REVIEW HAS NOT BEEN CORRECTED ON
 PLANS: SHEETS E-01 & E-02: #8 CONDUCTORS BETWEEN
 COMBINER PANEL AND INTERCONNECTION POINT ARE UNDERSIZED
 FOR 125% OF COMBINED INVERTER OUTPUTS, AND UNDERSIZED
 FOR 60 AMP OVERCURRENT PROTECTION. (34 IQ7+ INVERTERS @
 1.21 AMPS) X 1.25 = 51.4 AMPS. SEE TABLE 310.15
 (B)(16): USING 75 DEGREE COLUMN, # 8 AMPACITY = 50.
 OVERCURRENT PROTECTION FOR #8 (BASED ON 75 DEGREE
 TERMINATIONS) IS LIMITED TO 50 AMPS; 60 AMP IS REQUIRED
 FOR THIS SYSTEM. SEE 240.4 (B). USE #6 THWN CONDUCTORS
 FOR THIS APPLICATION.
  
2021-10-15 15:24:51.00000 
  
 REVISIONS 10/15/21 PERMITS@SUNVENA.COM
  
  