2021-12-08 16:26:49.00000CHARLES REVIEWED THE ELECTRICAL TODAY AND THIS IS HIS
 COMMENT: ELECTRICAL LAYOUT LOOKS OK; THE FOLLOWING
 LANGUAGE SHOULD BE ADDED TO SHEETS E-101 & E-102, OR
 INCLUDED IN REVIEW COMMENTS:
 "ALL BRANCH CIRCUITS SERVING PATIENT CARE SPACES SHALL
 COMPLY WITH THE EQUIPMENT GROUNDING PROVISIONS OF NFPA
 70, SECTION 517.13"
  
  