Plan Review Notes
Plan Review Notes For Permit 21100198
Permit Number 21100198
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-10-07 15:53:27.00000SHEET PV-05: SHOW DISCONNECTING MEANS/OVERCURRENT
 PROTECTION ON SUPPLY-SIDE OF COMBINER PANEL.
 DISCONNECTING MEANS SUPPLIED BY A LINE-SIDE TAP MUST BE
 LISTED SUITABLE FOR SERVICE EQUIPMENT (690.13 C), MUST
 HAVE A SHORT CIRCUIT RATING AT LEAST EQUAL TO THE
 AVAILAIBLE SERVICE SHORT CIRCUIT CURRENT (690.13 E),
 AND MUST BE LOCKABLE IN THE OPEN POSITION (705.22, ITEM
 7). IT CANNOT BE DETERMINED THAT THE INTENDED COMBINER
 PANEL MEETS THESE CONDITIONS.