2021-10-04 14:49:46.00000SHEET A-103: SHOW COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE 11.12.2.2.1 & 11.12.2.2.2.2: FOR EACH
 ROOF PLANE WITH A PV ARRAY, A 36" WIDE PATHWAY FROM
 GUTTER TO RIDGE SHALL BE PROVIDED . . . . FOR PV ARRAYS
 OCCUPYING MORE THAN 33% OF THE PLAN VIEW ROOF AREA, A
 MINIMUM 36" PATHWAY WHALL BE PROVIDED ON EITHER SIDE OF
 THE RIDGE.