Plan Review Notes
Plan Review Notes For Permit 21090792
Permit Number 21090792
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2021-12-20 16:20:20.000001] NEW 200A SERVICE DISCONNECT (ADJACENT TO METER) MUST
 SHOW NEUTRAL-TO-GROUND BOND.
 2] REMOVE NEUTRAL-TO-GROUND BOND IN ENPHASE SMART
 SWITCH.
 3] A NEUTRAL CONDUCTOR IS REQUIRED ON THE UTILITY SIDE
 OF BOTH COMBINER PANELS TO OPERATE THE ENVOY. SIZE
 NEUTRALS PER TABLE 250.102 (C)(1). MINIMUM #8 CU
 REQUIRED.
 4] AT THE PV DISCONNECT CONNECTED TO THE ENPHASE SMART
 SWITCH, INCLUDE A NOTE INDICATING THAT THE NEUTRAL IS
 NOT TO BE BONDED TO THE ENCLOSURE.
 5] AT THE PV DISCONNECT CONNECTED TO THE SUPPLY-SIDE
 TAP, INCLUDE A NOTE INDICATING THAT THE NEUTRAL IS TO
 BE BONDED TO THE ENCLOSURE. A SEPARATE EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN THE SERVICE AND THIS
 DISCONNECT IS NOT REQUIRED; BONDING TO EARTH IS
 ACCOMPLISHED BY THE NEUTRAL CONDUCTOR.
 5] THE STANDBY LOADS PANEL IS LABELED AS "100A", BUT
 CONTAINS A 200A MAIN BREAKER. PLEASE CLARIFY.