2021-09-28 16:21:04.00000SHEET E-1: #3 CONDUCTORS BETWEEN ENPHASE SMART SWITCH
 AND EXISTING PANEL ARE INCORRECTLY SIZED FOR THE 200
 AMP OVERCURRENT PROTECTION INDICATED.