Plan Review Notes
Plan Review Notes For Permit 21090367
Permit Number 21090367
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-09-16 13:28:49.00000SHEETS PV-04 & PV-05: #10 CONDUCTORS BETWEEN COMBINER
 PANEL AND PV DISCONNECT CANNOT BE FUSED AT 40 AMPS.
 LIMIT OVERCURRENT PROTECTION TO 35 AMPS (75 DEGREE
 RATING, NEXT HIGHER SIZE OCPD ABOVE REQUIRED MCA OF
 31.76) OR CHANGE CONDUCTORS TO #8 COPPER IF USING 40
 AMP FUSE.