Date Text
2021-09-16 12:35:06.00000SHEET PV-4: CHANGE CONDUCTORS BETWEEN INVERTER AND PV
 DISCONNECT TO MINIMUM #6 CU. (REQUIRED MCA = 52.5 WITH
 60A OCPD, #8 AS SHOWN MAX AMPACITY @ 75 DEGREES C IS
 50).