Plan Review Notes For Permit 21090217
Permit Number 21090217
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-09-09 16:30:18.00000SHEET PV-2. PROPOSED ROOF LAYOUT NOT COMPLIANT WITH
 FLORIDA FIRE PREVENTION CODE 11.12.2.2.2.2: "FOR PV
 ARRAYS OCCUPYING MORE THAN 33% OF THE PLAN VIEW ROOF
 AREA, A MINIMUM OF 36 INCH PATHWAY SHALL BE PROVIDED ON
 EITHER SIDE OF A HORIZONTAL RIDGE". ARRAY SECTION R1 OR
 R2 MUST BE MOVED AWAY FROM RIDGE TO PROVIDE
 REQUIRED PATHWAY ON EITHER SIDE OF RIDGE.
2021-09-09 09:28:40.00000APP & PLANS DROPPED OFF FOR REVIEW