Date Text
2021-09-02 13:16:19.00000THIS IS AN ALTERATION TO AN EXISTING PV SYSTEM
 INSTALLED UNDER PERMIT #20080288; APPARENTLY FOR THE
 PURPOSE OF ADDING AN ENERGY STORAGE SYSTEM.
 1] PROVIDE SOLAR PERMIT APPLICATION STATING EXACT SCOPE
 OF ALTERATIONS. ELECTRICAL ALTERATION PERMIT NOT
 APPROVED.
 2] SHEET PV-2.0: CONDUCTOR LABEL C1 (#2 COPPER) HAS
 INSUFFICIENT AMPACITY FOR THE CONNECTED OVERCURRENT
 PROTECTION.