2021-10-29 14:58:37.00000REVISION ADDING ENERGY STORAGE, SHEET PV-04.2:
 1] SUPPLY-SIDE TAP CONDUCTORS MUST TERMINATE IN AN
 OVERCURRENT DEVICE THAT LIMITS CURRENT TO THE CONDUCTOR
 AMPACITY. SHOW MAIN BREAKER IN ENPHASE SMART SWITCH OR
 OTHER OVERCURRENT PROTECTION FOR THESE CONDUCTORS. IF
 USING #2 AWG AS SHOWN, PROTECTION CANNOT EXCEED 110
 AMPS.
 2] CONDUCTORS SUPPLYING CRITICAL LOADS PANEL MUST HAVE
 OVERCURRENT PROTECTION NOT EXCEEDING THEIR AMPACITY. #3
 AWG SHOWN ON PLANS HAS A MAXIMUM ALLOWABLE AMPACITY OF
 100 AMPS.