-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 21090049
Permit Number 21090049
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-09-02 12:41:50.000001] SHEET PV-02: NOTE 3 REFERENCES "CONDUIT ON ROOF";
 PLAN STATES THAT THE GARAGE IS REMOTE FROM THE HOUSE.
 PLEASE CLARIFY IF SEPARATE BUILDING OR IF CONNECTED
 STRUCTURALLY.
 2] SHEETS PV-02 THROUGH PV-05: ASSUMING THAT THE REMOTE
 GARAGE IS A SEPARATE STRUCTURE, SHOW A GROUNDING
 ELECTRODE SYSTEM CONNECTED TO THE EQUIPMENT GROUNDING
 SYSTEM OF THE GARAGE ARRAY. SHOW ALSO A PV
 DISCONNECTING MEANS (CAN BE NON-FUSED) AT A READILY
 ACCESSIBLE LOCATION ON THE GARAGE. IT MUST BE
 PERMANENTLY LABELED AS A PV DISCONNECTING MEANS FOR THE
 GARAGE ARRAY.