Plan Review Notes For Permit 21090041
Permit Number 21090041
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-09-02 12:10:55.00000SHEETS PV-04 & PV-05: OVERCURRENT DEVICES RATED 55 AMPS
 ARE NOT MANUFACTURED AS A STANDARD NEC SIZE. SEE TABLE
 240.6 (A). FUSE RATING MUST BE 60 AMPS; RETAIN USE OF
 #6 CONDUCTORS.