Plan Review Notes For Permit 21080997
Permit Number 21080997
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2021-09-21 16:29:51.00000SHEETS PV-04 & 05: 125% OF COMBINED PV AND ENERGY
 STORAGE INPUT PLUS 175A MAIN BREAKER RATING EXCEEDS
 120% OF 200A BUS RATING. THE POSSIBILITY OF BOTH
 BATTERIES AND THE ARRAY EXPORTING TO UTILITY (WITH
 UTILITY POWER ON) IS ASSUMED. IS A SUPPLY-SIDE TAP
 POSSIBLE?
2021-09-17 10:42:28.00000RECEIVED REVISED PLANS JAIMEIE@LUNEXPOWER.COM