Plan Review Notes For Permit 21080537
Permit Number 21080537
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-08-17 16:15:30.00000SHEET E601: WITH SUPPLY-SIDE TAP, PV DISCONNECT MUST
 PROVIDE OVERCURRENT PROTECTION, MUST BE LISTED FOR USE
 AS SERVICE EQUIPMENT, AND MUST SHOW NEUTRAL-TO-GROUND
 BONDING.