Plan Review Notes For Permit 21080411
Permit Number 21080411
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-08-12 15:31:34.00000SHEETS PV-04 & PV-05: #10 CONDUCTORS FROM COMBINER
 PANEL TO PV DISCONNECT NOT APPROVED; CANNOT BE FUSED AT
 40 AMPS. REFER TO TABLE 310.15 (B)(16) AND 240.4 (D);
 NO EXCEPTION ALLOWED BY 240.4 (G). CHANGE CONDUCTOR
 SIZE TO #8 CU.