Plan Review Notes For Permit 21080095
Permit Number 21080095
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-08-11 14:01:55.00000REVISIONS SENT IN 8/11
2021-08-03 16:23:58.00000SHEET PV-04: EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT MUST BE MINIMUM #8 CU
 (TABLE 250.122). WHEN USING SUPPLY-SIDE TAP, BOND
 NEUTRAL TO PV DISCONNECT ENCLOSURE AND DO NOT INSTALL
 SEPARATE EQUIPMENT GROUNDING CONDUCTOR BETWEEN PV
 DISCONNECT AND SERVICE PANEL.
  