2021-07-21 16:18:44.00000SHEETS PV-04 & PV-05: #10 AWG CONDUCTOR BETWEEN
 COMBINER PANEL AND PV DISCONNECT MUST BE FUSED AT NOT
 MORE THAN 75 DEGREE C AMPACITY. USE 35 AMP FUSES OR
 REPLACE CONDUCTORS WITH MINIMUM #8 AWG.