Plan Review Notes
Plan Review Notes For Permit 21070595
Permit Number 21070595
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2021-07-21 14:59:37.000001] SHEET E-01, WIRE TAG #2: ADJUSTED/CORRECTED AMPACITY
 OF #10 CONDUCTOR (IN RACEWAY ON ROOFTOP) IS LESS THAN
 125% OF COMBINED INVERTER OUTPUT. USE HIGHER AMPACITY
 CONDUCTOR OR DIVIDE INVERTER STRINGS INTO MORE THAN ONE
 RACEWAY. SEE 690.8 (A)(3), SUBJECT TO 690.8 (B)(1) &
 (2).
 2] PLANS STILL DO NOT SHOW RAPID SHUTDOWN COMPLIANCE
 GRAPHIC LABEL PER FIGURE 690.56 (C)(1)(A).
  
  