Date Text
2021-07-20 15:37:59.000001] PLANS DO NOT INDICATE COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE SECTION 11.12.2.2.2. ROOF LAYOUT MUST
 SHOW FIRE ACCESS PATHWAYS AND TOTAL PERCENTAGE OF ROOF
 AREA COVERED BY ARRAY(S).
 2] ADD RAPID SHUTDOWN COMPLIANCE GRAPHIC LABEL PER
 690.56. THIS LABEL SHOULD BE SHOWN WITH APPLICATION
 INSTRUCTIONS ON SHEET E-03.