2021-07-19 14:51:34.00000CONTACT BART AT BART.SIMON@TOWEQUEST.COM
2021-07-19 08:35:21.00000SHEET E-2: #1 AWG CONDUCTORS FROM GENERATOR TO ATS ARE
 UNDERSIZED FOR 200 AMP OVERCURRENT PROTECTION ONBOARD
 GENERATOR