2021-07-13 15:27:42.00000PLEASE SPECIFY THE EXACT PRODUCT NUMBER OF THE INTENDED
 MICROINVERTERS. PLAN SHEETS A-1 & A-4 INDICATE "IQ7"
 ONLY. SPECIFY IQ7-60-2-US OR IQ7PLUS-72-2-US (MAXIMUM
 POWER OUTPUT DIFFERS BETWEEN THESE TWO INVERTERS).