Plan Review Notes For Permit 21070160
Permit Number 21070160
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-07-08 16:15:31.00000EMAILED IN FROM GOSOLAR@LUNEXPOWER.COM
2021-07-08 15:35:23.00000SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER PANEL
 AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF 125%
 OF COMBINED INVERTER OUTPUT (34 X 1.21 X 1.25 = 51.4).
 #8 AMPACITY @ 75 DEGREES C IS 50; EQUIPMENT TERMINAL
 TEMPERATURE RATING 75 DEGREES C. INCREASE CONDUCTOR
 SIZE TO #6.