Plan Review Notes For Permit 21070078
Permit Number 21070078
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-07-06 14:45:44.000001] SPECIFY TYPE OR OCCUPANCY OR PURPOSE OF BUILDING
 THAT PV MODULES WILL BE INSTALLED ON. IF USED AS
 DWELLING UNIT, FLORIDA FIRE PREVENTION CODE SECTION
 11.12.2.2 APPLIES REGARDING FIRE ACCESS PATHWAYS AND
 ROOF ACCESS POINTS.
 2] SHOW INSTALLATION OF A GROUNDING ELECTRODE SYSTEM
 CONNECTED TO THE ARRAY FRAME AT THE REMOTE BUILDING PER
 690.47.
 NOTE THAT THIS INSTALLATION WILL REQUIRE AN INSPECTION
 OF UNDERGROUND CONDUITS, EITHER BY SITE VISIT OR
 INSPECTION TUBES.