Plan Review Notes For Permit 21070077
Permit Number 21070077
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-07-06 14:28:07.000001] SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER
 PANEL AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF
 125% OF COMBINED INVERTER OUTPUT (34 X 1.21 X 1.25 =
 54.1). #8 AMPACITY @ 75 DEGREES C IS 50; EQUIPMENT
 TERMINAL TEMPERATURE RATING 75 DEGREES C. INCREASE
 CONDUCTOR TO #6.
 2] SHEETS PV-04 & PV-05: PV DISCONNECT PARAMETERS DO
 NOT MATCH.