Date Text
2021-07-06 14:23:57.00000SHEETS PV-04 & PV-05: CONDUCTORS BETWEEN COMBINER PANEL
 AND PV DISCONNECT MUST HAVE A MINIMUM AMPACITY OF 125%
 OF COMBINED INVERTER OUTPUT (24 X 1.21 X 1.25 = 36.3).
 #10 AMPACITY @ 75 DEGREES C IS 35; EQUIPMENT TERMINAL
 TEMPERATURE RATING 75 DEGREES C. INCREASE CONDUCTOR TO
 #8.