2021-07-02 15:14:55.00000SHEET PV-04 & PV-05: CHANGE PV DISCONNECT OVERCURRENT
 DEVICE TO 50 AMP. 60A OVERCURRENT PROTECTION NOT
 APPROVED FOR #8 CU WITH 75 DEGREE C TERMINALS.
 PROVIDE VALUATION FOR PERMIT APPLICATION.