Plan Review Notes For Permit 21061032
Permit Number 21061032
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-07-09 11:57:38.00000AT THIS TIME, PLANS ARE NOT APPROVED BASED ON COMMENTS
 BELOW AND FULL REVISIONS WILL BE REQUIED. IN SUBMITTING
 REVISIONS, ENSURE A LETTER IS PROVIDED RESPONDING TO
 THE CHANGES AND THE CHANGES WITHIN THE PLANS ARE
 CLOUDED. SHOULD ANYONE BELIEVE COMMENTS MADE ARE NOT
 REQUIRED, DOCUMENTATION SHALL BE SUBMITTED ALLOWING THE
 EXEMPTION.
  
 MISSING THE FOLLOWING INFOMATION AS PER NFPA 58:
 LIQUEFIED PETROLEUM GAS CODE, 2017 EDITION:
 1. LOCATION OF OTHER CONTAINERS ON THE PROPERTY
 2. THE DISTANCE BETWEEN THE TWO MAIN CONTAINERS
 3. TYPE OF CONTAINER, APPURTENANCES, AND REGULATORS
 4. SCHEDULES OF PIPING (INCLUDING FLEXIBLE CONNECTORS
 AND HOSE), LENGTH OF PIPING, HYDROSTATIC RELIEF VALVES.
  
 THE ORIGINAL DOCUMENTS HAVE BEEN SCANNED AND EVERYTHING
 GIVEN BACK TO CUSTOMER.