Plan Review Notes For Permit 21060083
Permit Number 21060083
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-06-02 14:22:50.00000SHEET E-01: #8 AWG CONDUCTORS BETWEEN SERVICE PANEL AND
 NEW LOAD CENTER DO NOT HAVE SUFFICIENT AMPACITY FOR PV
 SYSTEM. ALSO, PLEASE CLARIFY INTENT OF SHOWING A LOAD
 CENTER WITH A 70A MAIN PLUS A 70A PV BACKFED BREAKER.
 THIS INSTALLATION WOULD PROVIDE ADDITIONAL CIRCUIT
 BREAKER SPACES THAT COULD BE USED FOR FUTURE LOADS,
 THEREBY OVERLOADING THE BUSS. THE PV DISCONNECT SHOULD
 PROVIDE OVERCURRENT PROTECTION, CIRCUIT SPACES, AND A
 DISCONNECTING MEANS FOR THE PV SYSTEM ONLY.