Plan Review Notes For Permit 21050813
Permit Number 21050813
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-05-26 16:20:57.00000SHEET PV 4.0: #3 THWN CONDUCTORS INDENTIFIED AS "F" AND
 "E" DO NOT HAVE CORRECT OVERCURRENT PROTECTION. PROTECT
 AT MAXIMUM 100 AMPS OR REPLACE CONDUCTORS WITH 150 AMP
 RATED TO MATCH OVERCURRENT PROTECTION SHOWN.
 SYSTEM NOT RECOGNIZED AS A "STAND-ALONE SYSTEM" PER
 ARTICLE 710, SINCE LOADS IN BACKUP PANEL CAN BE
 SUPPLIED BY UTILITY.