Date Text
2021-06-24 14:16:30.00000PLAN REVIEW #:21050697-21050696-21050695-21050692
  
 PROJECT: STARFISH STORAGE
  
 LOCATION:5544 TANGLEWOOD DRIVE
  
 OCCUPANCY: STORAGE
  
 REVIEWED BY: FIRE MARSHAL MICHAEL RODDE
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 ______________________________
 AT THIS TIME THE PLANS ARE APPROVED.
 1. WATER SUPPLY SHALL BE ESTABLISHED ON SITE PRIOR TO
 ANY COMBUSTIBLES BEING BROUGHT ONTO THE SITE. FURTHER
 EMERGENCY ACCESS SHALL; BE PROVIDED TO THE SITE. THIS
 ACCESS SHALL BE MAINTAINED AND SUPPORT WEIGHT OF
 EMERGENCY APPARATUS.
 2. SAFEGUARDS FOR CONSTRUCTION SHALL BE IN PLACE IN
 ACCORDANCE WITH NFPA 1 AND NFPA 241, STANDARD FOR
 SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS. ENSURE CERTIFIED FIRE EXTINGUISHERS ARE
 PROPERLY LOCATED THROUGHOUT BUILDING DURING
 CONSTRUCTION AND NO SMOKING TAKES PLACE INSIDE THE
 BUILDING. NO SMOKING SIGNS SHALL BE DISPLAYED IN THE
 BUILDING. NFPA I: 16.1.1
 3. SEPARATE PLANS SHALL BE SUBMITTED TO OBTAIN PERMIT
 FOR UNDERGROUND FIRE LINE, FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.
 4. ALL ROOMS TO HAVE IDENTIFICATION PLACARDS WITH
 MINIMUM I INCH LETTERING WITH THE LIFE SAFETY EQUIPMENT
 LETTERING 4 INCHES AND IN RED.
 5. ENSURE ADDRESS IS LOCATED ABOVE MAIN ENTRY DOOR -
 MINIMUM 6 INCHES IN HEIGHT
 6. KNOX BOX IS REQUIRED AT MAIN ENTRY, REAR EXIT, AND
 FIRE RISER ROOM.
 ALL LIFE SAFETY FEATURES SHALL BE VERIFIED DURING
 CONSTRUCTION BY THE FIRE MARSHAL’S OFFICE.
 TO SCHEDULE AN INSPECTION, YOU MUST CALL THE FIRE
 MARSHAL’S OFFICE AT 863-402-7665 24 HOURS IN ADVANCE
 FOR AN APPOINTMENT.
  
  
 REVIEW FEE – 55 PAGES AT $20 = $1100 + INSPECTION FEE
 OF $55 = $1,155
  