Plan Review Notes
Plan Review Notes For Permit 21050153
Permit Number 21050153
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2021-05-07 16:00:00.00000SHEET PV-06: PLANS SHOW PV OVERCURRENT DEVICE IN
 EXISTING 100A LOADCENTER, NOT APPROVED WITH BUSS
 RATING. SHOW OVERCURRENT PROTECTION IN PV DISCONNECT
 ONLY. ALL ASPECTS OF ONE-LINE DIAGRAM MUST CLEARLY AND
 CONSISTENTLY INDICATE THE POINT OF CONNECTION AND THE
 LOCATION OF THE OVERCURRENT PROTECTION. PV DISCONNECT
 FOR SUPPLY-SIDE TAP MUST BE NO MORE THAN TEN FEET FROM
 TAP, AND SHOULD BE INDICATED ON DRAWINGS.
2021-05-06 07:51:17.00000EMAILED IN FROM PERMITTING@MERAKISOLUTIONS.COM